DSP-based dissipation factor and capacitance measuring system
|
Applications: |
- Measuring system operates fully automatically
- It displays relevant measuring quantities, such as dissipation factor, capacitance, test voltage and frequency
- Grounded test objects can also be measured
|
|
Specifications: |
- Measuring frequency range - 10 -400 Hz
- Maximum test current (r.m.s) - 1 A for f > 50 Hz (extension unit 15A on enquiry
- Measuring range : tan - 0,0000001 ... 100
- Resolution : tan - 0,0000001
- Measuring range : C - 0,1 pF ... 2 µF
- Resolution : C - 0,1 pF
- Cycle time of sucessive measurements, minimal - 1 measurement within 20 ms
- Capacity range of the standard capacitor - recommended value 100 pF
- Measuring accuracy loss factor - ±( 0,01 rdg + 0,0000001 )
- Measuring accuracy test voltage - ±( 0,005 rdg + 1 V )
- Measuring accuracy capacity - ±( 0,001 rdg + 1 V )
- Measuring accuracy frequency - ±( 0,0001 rdg + 1 mHz )
- Signal processing - Digital signal processor (DSP), Industrual-PC (Pentium)
- Display - Flat panel (TFT)
- Data storage - Hard disk, Floppy disk drive
- PC-compatible interfaces - printer, V.24 / RS232C
- Operating system - MS Windows NT 4.0
- Supply voltage - 115 V / 230 V, 50/60 Hz, ca. 60 VA
Return to top
|
|
Characteristics: |
- Full automatic, high accurate computer-aided measurement in the frequency range between 10 to 400 Hz
- Integrated digital signal processor (DSP) permits the evaluation of the data within each cycle of the applied AC test voltage (20 ms)
- Status of frequency selective measurements on FFT-basis which reduces the interference by harmonics superimposed to the test voltage
- Comprehensive information also in magnitude and frequency of the test voltage
- Graphic user interface displaying the spectrum and the time dependent trend of the dissipation factor and capacitance as well as the time
function of the test voltage
- Integrated hard disk and floppy disk are used for data storage and file transfer
Return to top
|
|
|
|