On-site and Laboratory PD diagnosis tests
|
Applications: |
- Detection of dangerous partial discharges (PD)
- Mode for differential measurement with respect to PD fault location
- Diagnostics on HV apparatus in field (for instance cable sealing ends and joints,
surge arrestors, power transformers, voltage transformers and electrical machines)
- Evaluation of the PD behaviour of low voltage components (for instance in the case of opto-couplers,
capacitors, transformers and motors)
|
|
Specifications: |
- Detection of the electromagnetic transients of PD events
- Measuring the PD quantity "apparent charge"
- Exchangeable capacitive and inductive sensors
- Potentialfree signal transmission via fibre optic link
- Noise reduction mode
- Measuring sensitivity if charges pulses are directly injected : 0,05 pC
- Gain steps : 1, 2, 5, 10
- Vernier range : 1 : 5
- Output (CHARGE) at full load
- Pulse shape : triangular, positive
- Pulse magnitude : 4 V approx.
- Pulse rise time : < 2 µs
- Pulse duration : 50 µs approx.
- Noise level : < 0,2 V
- Pulse resolution performance for superposition error < 30%
- Pulse repetition rate : < 100 kHz
- Double pulse distance : > 2 µs
- Power supply : 8 Mignon batteries (LR6)
- Dimensions : 220 × 60 × 100
- Weight : 1 kg approx.